Details
Kentec Syncro Multi Input/Output Unit (MIOU)
Occupying less than 20% of the space required by conventional I/O units, the MIOU replaces the large and expensive enclosures normally required for this application.
With 8 opto-isolated inputs and 8 volt-free relay contacts (relay output individually selectable as normally open, normally closed or switched voltage outputs), the MIOU will find a multitude of uses in concentrated I/O applications.
Features:
- Multiple inputs and outputs at one address
- Opto isolated inputs
- Volt free contact or switched voltage outputs
- Considerable space and cost saving over discreet I/O units
- Easy clip-on din rail mounting method
- Compatible with Solo, Syncro AS and Syncro control equipment
- Low standby supply current
- Hochiki ESP protocol
Technical Specifications:
- Dimensions: K559: 203L x 77W x 45D, H66000M2/H66750M2: 385L x 310H 90D
- Boxed unit battery capacity: 2.6Ah 12V (2 per unit)
- Finish - lid & box: Epoxy powder coated
- Colour - lid & box: BS 00 A 05 grey - fine texture
- Boxed unit IP rating: IP30
- Module mounting: Symmetrical or asymmetrical din rail
- Communication protocol: Hochiki ESP
- Supply voltage H66000M2: 24V DC
- Supply voltage H66750M2: 110 or 230V AC 50 or 60Hz (specify when ordering, default is 230V)
- Quiescent supply current: 10 milliamps
- Input operated current: 3 milliamps
- Output operated current: 18 milliamps
- Input trigger resistance: 1k maximum
- Output contact rating: 30V DC 1 Amp maximum
- Switched -ve output: 65 milliamps maximum per output
- Minimum recommended PSU: 750 milliamps at 24V DC
- Operating temperature: -5 to +40°C
- Device sub-address count: 17 (of 800 permitted in Syncro/Syncro AS panel)
- Address setting: Hochiki hand held programmer (TB1010)
Additional Information
| Model | K559 |
|---|---|
| Suggested Use | Commercial |
| Manufacturer | Kentec |
| Compliance | N/A |
| CE Approved | Yes |
Questions on Kentec Syncro Multi Input/Output Unit (MIOU)
No questions asked yet
Ask Your Own Question
: Empty