PE8 Premier Elite 8 Zone Fire Alarm Panel
The Premier Elite 8 zone fire alarm panel is ideal for small to medium sized installations. They meet all the requirements of EN54 parts 2 & 4, and come in an attractively styled enclosure.
In addition to the Premier Elite 1-2 zone features, the 8 zone version also has:-
Fault Relay
Current limited charger to prevent fl at batteries drawing too much current
Built in diode base compatibility
Sounder Delay facility
Connection to optional add on zonal output card.
Zone disablement facility
One man test facility.
The zonal output card gives a drive voltage to operate zonal alarm relays, or a hardwired repeater panel.
Specification
Supply Voltage: 230V AC +/- 10%
System Voltage: 29V DC (Nominal)
Detection Zone: 8
Zone Voltage: 22V DC
Zone End Of Line: 1N4002 Diode
Sounder Output: 2 X 400mA @ 24V DC
Sounder EOL: 10 K Resistor
Sounder Delay: 0 to 9 minutes
Fire Relay: 1 Relay, Selv @ 1A
Fault Relay: 1 Relay, Selv @ 1A (Normally Energised)
Other Connections: Class Change Input (N/O Contact), Zonal Output Card Interface (20 WY Ribbon)
Operating Temperature: -0°C to 50°C
Enclosure Size: 355 X 275 X 100mm
Weight: 3.25 KG
|